CCD-020
Conventional fire alarm control panel for 2 zones mounted on ABS plastic housing. Discriminates between detector alarm and manual call points alarm. Up to 32 detectors per zone. It has 2 configurable supervised sounder outputs (500 mA each output), alarm and fault relay outputs free of voltage, auxiliary 24V output (500 mA maximum consumption), 24V resettable output (500 mA maximum consumption). Sounder output delay configurable on board. Multilingual keyboard. CPR certificate EN54-2 and EN54-4. Dimensions: 282 x 240 x 102 mm. Requires 2 BTD-1202 batteries (not included).
The range of compact conventional control panels ECO series of Detnov allows to cover all the requirements of small
installations.
There are two models in this range: CCD-020 (2 zones) and CCD-040 (4 zones). CPR EN 54-2 and EN 54-4 approved.
Up to 32 detectors or 10 manual call points can be connected per zone. Discriminating between manual call point alarm
and detector alarm. There is a relay output for alarm status and another for fault status, 2 monitored sounder outputs
(500 mA each output) and a 24V auxiliary power output (500 mA).
Compatible with installations that have already been build by other manufacturers with a 4k7 Ω resistance at the end
of the line.
A sounder activation delay of 0 to 10 minutes (1 minute blocks) can be set.
There is a "Test" function for straightforward maintenance by a single person, with the control panel resetting just a few
seconds after the detector has been tripped.
°° 2 and 4 zone models
°° Discrimination between detector or manual call point alarm per zone
°° Alarm status relay output
°° Fault status relay output
°° 2 supervised sounder outputs (500 mA each output)
°° 24V auxiliary power output (500 mA)
°° Test function for maintenance
°° Multilingual keyboard
°° ABS plastic box
°° EN 54-2 and EN 54-4 approved