DMT-FP9000-8

  • Conventional central 8 areas with LCD screen
  • 2 Siren output
  • 2 alarm and fault outputs and 2 configurable relay outputs
  • Repeater output
  • Up to 30 detectors per zone
  • End-of-line resistance auto detection

  • DMTECH
  • Conventional fire alarm panel of 8 zones
  • Certificate EN54-2 and EN54-4
  • 2 independent siren outputs
  • 2 auxiliary alarm and fault outputs
  • 2 configurable relay outputs
  • Individual output for repeaters
  • Capacity for 2 12V batteries
  • 4 access levels ((3 user and 1 manufacturer)
  • LCD display with menu for advanced programming
Primary power supply Switching source 187-252V AC 50-60 Hz 65W max.
Backup power supply 2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration.
Available languages English, French, Spanish, Turkish, Romanian and Russian.
Number of zones 8 zones, up to 30 detectors by area.
Siren outputs 2 siren outputs 24VDC. Independent and monitored open collector outputs
Relay outputs 4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max.
End of line resistance Areas fully monitored by end-of-line resistance (4.7K)
Auxiliary Output Voltage 24VDC. Protected by resettable electronic fuse 1.85A
Protection Index IP30
Temperature -5ºC~+45ºC
Material and colour ABS, colour: White
Dimensions 310 x 240 x 80 mm
Weight 1,3Kg
Recommended cable Fire cable with a minimum section of 1.0mm (18AWG).

WRITE YOUR OWN REVIEW

How do you rate this product? *