11340
- Power supply: 230V 50 Hz + 10% - 15% 500 Ma
- Power supply backed up by 2 NI-MH 9V 280mAh batteries
- Configuration of each input (NO or NC contacts) and time delay
Technical alarm panels are used in any type of building (boiler room, elevator, technical rooms, etc.) to report technical faults in an installation.
They allow the signaling of an alarm from a normally open or closed potential-free contact. A specific indicator light indicates a possible fault with the mains or battery power supply. The front of the product allows you to enter the labels of the zones or alarms reported.
- Possibility of installing the product at a 90 ° wall angle
- Integrated installation aid instrument (spirit level)
- Power supply backed up by Ni / Mh battery
- Summary relay for reporting all faults (supervision, remote monitoring center, etc.)
- Configuration of each input (NO or NC contacts) and time delay
- 3 LEDs (power on, mains fault, battery fault)
- 4 or 8 warning lights
- 1 Buzzer
- 1 Multifunction button: LED test, audible signal stop and alarm reset
- Connection of inputs / report: 1 pair 8 / 10th (1000m max)
- Connection information report: 3G 1.5 mm²
- User output 19V +/- 3V: 60mA
- Report output: bus for report 10540/10580
- Material / Color: PC / White
- Operating temperature: -10 ° C to + 55 ° C
- Protection index: IP 40 / IK 07
- Weight: Net - 760 g Gross - 860 g
- Dimensions: (mm) H 258 x W166 x D 84