C404
Fire detection control units C402 and C404 control up to two and four independent zones, respectively, with 32 devices per zone as a maximum. Each line is considered as a zone and can be either activated or deactivated via a command from keypad. The control unit has two outputs: one general alarm siren output activated with at least one zone in alarm condition and one general malfunction siren output activated when a malfunction condition occurs either on the control unit or in a zone. General alarm siren output can be either activated or deactivated via keypad. Other outputs (relay, general alarm and zone alarm) are available on optional relay board. It is possible, for each single zone independently, to decide whether the alarm notification is to be sent with one alarmed device only (single consensus) or with at least two alarmed devices (double consensus). This helps prevent false alarms.
Certified EN54 part 2 and part 4. No.0051-CPD-0337
Power supply: 26.4 Vdc
Double threshold balanced lines
Pre-alarm absorption (single consensus): 20 mA
Alarm absorption (double consensus): 40 mA
Supervised siren output: 24Vdc @ 500 mA
Field output: 24 Vdc @ 500 mA
Malfunction relay output: 24 Vdc @ 1 A
Electric output protection
Memoria non volatile
Non-volatile memory
Battery charge limit
Programming keypad
Exclusion of single lines
Zone notifications: LED
Battery housing: 2 x 7 A - 12 Vdc batteries
Operating temperature: -5° ÷ +50° C
Material: ABS
Dimensions (W x H x D): 340 x 240 x 96 mm