FDGPL400

LPG gas detector fitted with base with relay output The FDGPL400 detectors allow to signal the presence of LPG concentrations lower than the lower explosive limit (L.E.L.), i.e. 10%, long before an explosive mixture is composed. The detector is equipped with a relay alarm output with contact exchange (NO and NC), a malfunction output with optically isolated NC contact and two terminals to connect a power absorption line for conventional control units.

Supply voltage: 11 ÷ 29 VDC

Absorption at rest: 60mA at 12 VDC - 30mA at 24 VDC

Alarm absorption: 70mA at 12 VDC - 40mA at 24 VDC

Line alarm absorption: 50mA at 24 VDC

Delay for alarm: 20 seconds

Delay for alarm reset: 30 seconds

Alarm threshold for detection: 10% LEL – 0.18% in volume

Alarm relay output: (NO-NC) 1A, 30 VDC resistive load

Malfunction output: optically isolated NC contact 20mA, 30 VDC

Operating temperature: 0 ÷ 40°C (max* -15 ÷ 55°C)

Humidity: 30 ÷ 95% (max* 0 ÷ 95%)

Weight: 110g

White ABS casing

Protection class IP30

Dimensions Ø 90 x h 48 mm (base included)