FAP544

Microprocessor control unit with 2 loop lines expandable to 4 Possibility of managing up to 128 points per loop (512 points max) 

Microprocessor control unit with 2 loop lines expandable to 4 Possibility of managing up to 128 points per loop (512 points max) Self-learning of the devices in the field Graphic display 240 * 128 - 4.7 "backlit History log: 1,000 events Chronological view that can be viewed directly from display 10 programmable passwords on 3 levels 480 programmable zones, 240 groups of zones, 240 groups of points USB port for local PC connection to program via dedicated software Possibility to monitor the level of the signal / noise ratio of the sensor Real time clock integrated with buffer battery Non-volatile memory Control unit outputs: alarm, siren, fault, programmable (mains failure / exclusion) Internal buzzer Exclusion of the single point / zone Power supply: 230Vac Maximum deliverable current: 1.5A @ 24Vdc Limitation of the battery charge and control of their status Accumulator housing: 2 batteries of 12 @ 12Vdc Possibility of creating a loop of max 2 Km with shielded 2x1.5mm cable Immunity to disturbances up to 30Vm Common dialogue protocol for all control units system Dimensions: 490 (L) x 350 (H) x 145 (D) mm EN54 certified part 2 and 4 (0051-CPD-0239)

Basic configuration: 2 loop lines (class A) or 4 open lines (class B)

Maximum configuration: 4 loop lines (class A) or 8 open lines (class B)

Possibility of managing up to 128 points per loop

Point teach-in and point logic address

240*128 - 4.7 “ backlit graphic display

Event log: 1,000 events

Event history shown on display

10 passwords programmable on 3 levels

480 programmable zones

USB port for connection to local PC for programming via SW

Possibility of monitoring detector signal/noise ratio level

Built-in real time clock with buffer battery

Non-volatile memory

Alarm data saved on devices

Monitoring of the first 10 devices entering alarm status with graphic and digital time-trend visualisation

Control unit outputs: 4 [siren relay, alarm relay, malfunction relay, programmable relay (power
failure/exclusion)]

Internal buzzer

Exclusion of individual point /zone

Power supply: 230 Vac

Maximum output current: 1.5 A @ 24 Vdc

Battery charge limit and battery status check

Battery housing: 2x 12 A @ 12 Vdc batteries

Possibility of implementing at least 2 Km loop with 2 x 1.5 mm2 screened cable

Noise immunity up to 30 Vm

Communication protocol shared by all system control units

Dimensions (W x H x D): 490 x 350 x 145 mm

Certified EN54 part 2 class and part 4, No. 0051-CPD-0239