FL100
FL100 smoke linear detector is mainly suitable for office building applications. Its operating principle is based on the interaction between the smoke present inside a room originated by an incipient fire and an infrared emitted by a transmission unit (Tx) and received and duly processed by a receiving unit (Rx). In particular, the Rx receiver processes an electric signal proportionally to the received light intensity, through the notification of an alarm or fault condition if the signal drops continuously below an alarm or fault threshold for a pre-set time period. The detector is equipped with three LED indicators and two 7-segment displays to report various information to the installer/operator. It also features a fault relay and 2 relays signalling the pre-alarm and alarm condition; the device features the connection to a standard fire detection line to signal the alarm condition to the control unit.
Supply voltage: 10.8 ÷ 26.8 Vdc
Consumption in stand-by mode at 24 Vdc: 55mA
Consumption in stand-by mode at 12 Vdc: 45mA
Consumption in alarm conditions at 24 Vdc: 60mA
Consumption in alarm conditions at 12 Vdc: 50mA
Consumption in fault conditions at 24 Vdc: 45mA
Consumption in fault conditions at 12 Vdc: 40mA
Pre-alarm shading thresholds: 20%, 25%, 30%, 35%
Alarm shading threshold: 35%
Minimum operating distance: 5 metres
Maximum operating distance: 150 metres
Transmitter beam wavelength: 890 nm
Beam misalignment tolerance: ±1°
1A pre-alarm relay, 30 Vdc resistive load - NO/NC contact to be selected through jumper
1A alarm relay, 30 Vdc resistive load - NO/NC contact to be selected through jumper
1A malfunction relay, 30 Vdc resistive load - NO/NC contact to be selected through jumper
Conventional line - input voltage range: 10 ÷ 20Vdc
Conventional line - absorption in pre-alarm conditions: 20mA at 20Vdc
Conventional line - absorption in alarm conditions: 40mA at 20Vdc
Conventional line - reset pulse duration: 200mS
Operating temperature range: (-10 ± 3)°C ÷ (55 ± 2)°C
Relative humidity: (93 ± 3)%
Protection class: IP55
Dimensions (W X H X D): 248 x 122 x 120 mm
Weight: 900g
Certified in compliance with EN54 part 12, No. 1293-CPR-0406